If you manage fire doors in London, sooner or later one of them will look the worse for wear. A chipped edge. A gap you can see light through. A door that no longer closes by itself. The next step is not always obvious. Do you repair it, replace it, or survey every door in the building?
The answer depends on what is wrong with the door, what it was originally, and what paperwork you hold for it. This guide explains how to weigh those up, so you can spend money where it protects people and avoid spending it where it does not.
How to Tell Whether a Fire Door Is Still Doing Its Job
A fire door only works as a complete assembly. The leaf, frame, seals, hinges, closer and any glazing all have to be correctly matched and fitted. If one part fails, the whole door can fail with it.
You can run a useful first check without any specialist equipment. Look for the following:
- Small, even gaps around the leaf. The manufacturer sets the tolerance, usually around 3mm.
- Intumescent strips and smoke seals that are present, undamaged and not painted over.
- A closer that brings the door fully shut and latches it without help.
- Secure hinges, usually three on a timber door, with no missing screws.
- A leaf, frame and glazing free of cracks, holes and damage, with a label or paperwork showing the rating.
Spotting a problem is the easy part. Deciding what it means takes more experience, which is why many landlords train their caretaking and maintenance teams to know what to look for. Isoler’s ASFP-accredited training covers fire doors, and suits teams who want to catch problems earlier.
When a Fire Door Can Be Repaired
Repair makes sense when the leaf and frame are sound and the fault sits in a part that can be replaced like for like. That covers worn or missing seals, failed closers, loose hinges, damaged ironmongery and minor surface damage.
The phrase that matters is like for like. A repair has to restore the door to the performance it was tested to achieve. Using the wrong seal, the wrong fixings or a filler that was never part of the tested construction can leave you with a door that looks repaired and no longer holds its rating. The work needs to follow the manufacturer’s guidance and be done by someone who knows it.
Some repairs involve no new parts at all. Doors expand and contract with changes in temperature and humidity, so a door that once fitted correctly can drift out of tolerance and leave a gap that is too wide. Easing and adjusting the door is often enough to bring it back. Where the gap at the bottom is too large, a drop down seal can be fitted to close it.
Repair also has practical advantages. In an occupied block it’s quicker and less disruptive than replacement, and residents lose less access to their homes. It is also the sensible route when most doors in a building are in reasonable condition and only a handful need attention.
Isoler’s fire door installation and maintenance service works on this basis. Where an existing door can be brought back to the required standard, we repair it. Where it cannot, we say so. We carry out routine assessments on doors in buildings of all ages.
When Replacement Is the Right Call
Replace the door when you cannot show that it is a certified fire door, when the damage goes through the leaf or frame, or when repair would cost close to a new door.
Certification is the one that catches people out. A door’s fire rating comes from the tested construction of the whole door set. Adding an intumescent strip to an ordinary door does not turn it into a certified fire door, and a door with no label and no paperwork is very hard to defend if someone asks. In older buildings, original timber doors are often assumed to be fire doors because they are thick and heavy. Thickness is not proof.
Other warning signs include large holes cut for letterboxes or vents, a leaf trimmed to fit an uneven frame, a door and frame from different manufacturers, or a rating lower than the fire strategy now requires, such as an FD30 door where an FD60 is needed.
When you do replace, the new door set should be certified, installed by competent fitters and supplied with paperwork you can file. Isoler fits compliant, certified fire doors, with the process supported by BM Trada accreditation.
Statutory Checks in Buildings Over 11 Metres
In multi-occupied residential buildings over 11 metres, the law sets how often fire doors must be checked. Communal fire doors need inspecting every three months, and flat entrance doors every 12 months. These requirements come from the Fire Safety (England) Regulations 2022. Flat entrance checks are made on a best endeavours basis, because access depends on residents.
The checks exist to confirm each door is compliant, and any defects found should be repaired. Skipping them carries a second risk. If the statutory inspection regime is not met, the original grading of a certified door installation could be void, because the doors would be treated as not having been maintained. A certified door that nobody looks after may stop counting as one.
Smaller buildings are not left out. Wherever a building has two or more homes, residents should still be given information about the importance of fire doors at least once a year, whatever the height.
When to Commission a Fire Door Survey
Commission a survey when you don’t know the condition of the doors across a building, or when one bad door suggests there may be more. Fixing doors one at a time as they fail is slow, and it leaves you guessing about the rest.
A fire door survey records every door in the building. Each one gets a location, a condition rating, a list of defects and a recommended action: repair, adjust, replace or no action. Photographs support the findings, and the output is a prioritised schedule you can cost, programme and work through.
Common triggers include taking on a new building, a fire risk assessment that has flagged doors, or an insurer asking for evidence.
One limit is worth knowing. A survey alone does not certify a door. The original installation or manufacturer’s paperwork has to be available for a surveyor to certify it. Where that paperwork is missing, a door can be classed as a notional fire door, but it will never reach certified status without installation or manufacturer’s records.
Isoler’s compliance team carries out fire door surveys alongside passive fire stopping and compartmentation surveys, which suits buildings where the doors and the walls around them both need checking. If a survey follows a fire risk assessment, our guide to what happens after a fire risk assessment explains how to turn findings into completed actions.
Fire Doors in London Buildings: Older Stock and Conversions
London’s building stock raises more fire door questions than most places, because so many buildings are used differently from how they were first designed. Houses have been converted into flats. Offices have become homes. Blocks mix residential floors with shops or offices below. Each change can alter where fire doors are needed and what rating they should have.
Older buildings add another layer. Original timber doors may be decades old, repeatedly painted, altered by past occupiers and missing any paperwork. Some may never have been fire doors at all.
As the enforcing authority in the capital, the London Fire Brigade can ask to see the fire risk assessment and the evidence that actions on doors have been followed up. A clear record of surveys, repairs and replacements is the simplest answer to that request.
The door is only one part of a fire compartment. If the wall or ceiling around it has unsealed gaps, the door cannot do its job alone. Fire stopping and compartmentation and fire doors should be looked at together.
Fire doors are one of several areas where buildings commonly fall short. Our post on the compliance gaps most buildings miss covers the wider picture.
Choosing a Fire Door Contractor in London
Ask for evidence rather than promises. A good contractor can show third-party accreditation, name who will carry out the work, and describe the paperwork you will receive at handover. Useful questions include:
- Which accreditation scheme covers the installation, and will you provide certificates for the doors?
- Who will fit them, and what training do they hold?
- What records will I receive when the job is finished?
Vague answers to any of those are worth taking seriously.
Isoler has opened an office on Kirby Street in London, supporting clients across London and the surrounding areas, and brings substantial experience of fitting and maintaining fire doors across the construction and social housing sectors. That includes maintaining 14,000 fire doors for Gentoo Group on the Genforce remediation project, which began in April 2023. If you want an independent view before committing to repair or replacement, our compliance professional services team can review your existing documentation and recommend next steps.